Skip to content
Heat Pump Electrical

Heat Pump Electrical Install London — ASHP Supply, Circuits, G99

The electrical side of heat-pump install — dedicated circuits, board upgrades, three-phase where the load demands it, G99 DNO liaison and BUS £7,500 grant paperwork. NICEIC-certified across London.

A modern air-source heat pump for a typical London 3-bed semi runs at 3–6 kW of continuous electrical input across the heating season, with a peak draw of 8–10 kW on the coldest mornings when both the compressor and the supplementary immersion are calling. Larger detached properties (8–12 kW heat output ASHP) can peak at 12–15 kW electrical input. On a 100A single-phase London supply, the heat-pump load competes with the EV charger, the induction hob, the kettle and the immersion — and on the worst-case January morning the household trips the cut-out fuse unless the supply is sized for it.

The decision tree splits at supply size. Most London terraces and 1960s–80s semis are on a 60A or 80A single-phase supply — fine for a small (5–7 kW) ASHP with weather compensation, smart-load control and a small immersion backup, marginal once you add an EV. A 100A single-phase supply (newer properties, post-meter-upgrade properties) comfortably handles a 7–9 kW ASHP plus a 7 kW EV charger with smart load balancing. Beyond 9 kW heat output — common on detached 4-bed-plus properties — a three-phase upgrade is usually the right answer, both for headroom and for the lower per-phase current draw at the compressor inrush. We size the supply at survey, not retrospectively.

DNO consent is governed by G98 / G99. ASHP units below 16A per phase notify under G98 — fast-track, no DNO pre-approval needed. Above 16A per phase (most 8 kW+ ASHPs and all three-phase units) requires full G99 DNO application before installation. The Boiler Upgrade Scheme (BUS) grant of £7,500 for air-source and £7,500 for ground-source heat pumps remains live through 2028 and is administered via Ofgem — the install must be MCS-certified (MIS 3005) and the property must be in scope. We handle the G99 application, BUS grant paperwork and the MCS commissioning sign-off.

Why Electrician London

Dedicated ASHP circuit

Dedicated 32A or 40A radial circuit from the board to the heat pump isolator with a Type A RCBO — separate from the rest of the household load.

Three-phase upgrade where needed

For 9 kW+ ASHPs or where the existing single-phase supply is already maxed by EV + hob load, we coordinate the DNO upgrade to three-phase.

G99 DNO liaison

Full G99 DNO application for installations above 16A per phase — UKPN, SSEN or others. We handle the paperwork and the site witness.

BUS grant documentation

MCS-certified install (MIS 3005), commissioning certificate, BUS application support and Ofgem submission — landlords and owner-occupiers eligible.

Heat pump electrical works pricing

Electrical-side prices only. The heat pump unit, hydraulic install and refrigerant work are quoted separately by the MCS-certified ASHP installer we partner with.

Dedicated ASHP circuit (32A + isolator)

New radial from board, Type A RCBO, lockable isolator at the unit

From £495

Fuse board upgrade for ASHP

Type A RCBO board with spare ways for ASHP + future EV

From £750

Three-phase supply upgrade for ASHP

DNO three-phase head, TP&N consumer unit, all internal works

From £4,995

G99 application support

DNO application, single-line diagram, commissioning witness

£225

BUS grant paperwork support

Ofgem application, MCS commissioning, supplier documentation

£150

What's included in heat pump electrical works

  • Pre-install load assessment
  • Existing supply size verification
  • Single-phase headroom calculation
  • Three-phase upgrade scoping where applicable
  • Dedicated radial circuit to ASHP isolator
  • Type A RCBO and lockable isolator
  • Weather-compensation control wiring
  • Immersion-backup circuit if specified
  • DNO G98 or G99 application
  • BUS grant documentation pack

Frequently asked questions

Do I need three-phase electricity for an ASHP?

It depends on the heat output of the unit and the rest of the household load. A 5–7 kW ASHP comfortably runs on a 60A or 80A single-phase supply with a smart-load module. An 8–9 kW ASHP works on a 100A single-phase supply with careful load management. A 10 kW+ ASHP or any ASHP installed alongside a 7kW EV charger and an induction hob on a 60–80A supply usually benefits from a three-phase upgrade — both for headroom and for the lower per-phase inrush current at compressor start.

Maximum ASHP size on single-phase?

Strictly: any ASHP with input current below 16A per phase notifies under G98 and no DNO pre-approval is needed. Above 16A per phase, G99 applies — most 8 kW+ output ASHPs hit this threshold. Practical maximum on a 100A single-phase London supply is around 12 kW heat output (≈ 25–30A peak input) with smart load balancing — beyond that the three-phase upgrade case is strong.

Boiler Upgrade Scheme — am I eligible?

BUS provides £7,500 toward an air-source heat pump and £7,500 toward a ground-source heat pump install in England and Wales. Eligibility requires: a domestic property in scope (including BTL), a valid EPC (no F or G rating), no outstanding loft or cavity insulation recommendations on the EPC (unless exempt), and the install must be MCS-certified. Larger commercial premises use the Public Sector Decarbonisation Scheme route instead.

What does the dedicated circuit need?

A dedicated radial circuit from the consumer unit to a lockable isolator within 2 metres of the ASHP outdoor unit. Cable size sized to the manufacturer’s rated input plus 25% headroom and the route length (typically 6mm² for a 5–7 kW unit, 10mm² for an 8–10 kW unit). A Type A RCBO at the board provides 30 mA leakage protection and overcurrent. Single-pole isolator at the unit allows safe maintenance. BS 7671:2018 + A4:2026 compliant.

Where should the isolator be?

Within 2 metres of the outdoor unit, in line of sight, lockable in the off position, and accessible without tools. The lockable requirement means the engineer servicing the refrigerant circuit can secure the supply against accidental re-energisation. We install the isolator on a weatherproof IP65 enclosure on the wall closest to the ASHP unit.

Weather compensation control wiring — what is involved?

Weather compensation modulates the flow temperature against the outdoor temperature — the single biggest determinant of seasonal coefficient of performance (SCOP). Most modern ASHPs ship with a weather sensor that wires from the outdoor unit to the controller — typically 2-core 0.5mm² screened cable, separate from the power circuit, with the sensor mounted on a north-facing external wall. We run the control cabling at the same visit as the power circuit.

Do I keep the hot water cylinder immersion as backup?

Best practice — yes. The immersion remains on its own dedicated circuit (usually 3 kW / 16A) as legionella-defence on weekly schedule and as cold-snap backup if the ASHP defrosts or trips. We size the immersion circuit and the ASHP circuit independently so both can run simultaneously without exceeding board limits.

Does the install need to be MCS for the grant?

Yes — strictly. BUS, SEG (for any solar PV that is part of the package) and most BTL lender refinance favouring depend on MCS certification. For ASHP, MCS scheme MIS 3005 applies; we work with MCS-certified ASHP installers and handle the electrical side of the install under the same MCS umbrella project number.

Heat pump topic cluster

The cost, grant and comparison guides every London household weighs before committing to an ASHP — plus the supply and EPC context the electrics depend on.

Related services

NICEIC engineers, same-day across London.

Director-led, no call-centre. Same-day digital certificate, no upfront payment.

Call 020 3633 5557