Skip to content
EICR

Garden Electrical Installation London — BS 7671 Section 705

Outdoor electrical work — sockets, garden lights, EV chargers, garden offices. The BS 7671 rules, SWA cable runs, and what a proper London install looks like.

6 min readReviewed by James Whitfield, Director & Qualifying Supervisor

BS 7671 outdoor basics

Garden circuits fall under general BS 7671 rules plus Section 705 (agricultural/horticultural — relevant for greenhouses) and Section 753 (heating cables, e.g. outdoor underfloor).

Every outdoor socket and lighting circuit must have 30 mA RCD protection. Type A RCD required from BS 7671:2018 + A4:2026 (October 2026) where DC fault current is foreseeable.

Fittings must be IP44 minimum for splash-resistance. IP65 for fully exposed locations.

Cable runs underground must be SWA (Steel Wire Armoured) or buried in conduit at minimum 600mm depth.

SWA cable run — the standard

SWA cable is the workhorse for outdoor circuits. Steel wire armour provides mechanical protection plus an additional earth path.

Typical sizing: 2.5mm² SWA for sockets up to 32A, 4mm² for high-load circuits like EV chargers, 6mm² or 10mm² for sub-mains feeding garden offices.

Burial depth — 450-600mm minimum to BS 7671. Use marker tape 150mm above the cable to warn future excavators.

Glands at every entry/exit — the SWA armour clamps into a gland that bonds the armour to earth. Loose glands are a common EICR finding.

Cost per metre installed: £18-28 for 2.5mm² SWA, £25-40 for 4mm², £40-60 for 10mm². Add £100-200 for trench preparation per 10m run.

Garden office sub-mains

A garden office is effectively a new sub-installation. Treat the run as a sub-main feed from the main consumer unit to a sub-board in the office.

Typical sub-main: 10mm² SWA from house consumer unit to garden office sub-board. Feeds a 40-60A circuit.

Sub-board in the office: small 4-6 way consumer unit with RCBOs for lighting, sockets, heating.

Heating in garden offices is usually electric (panel heaters or low-temperature underfloor). Heat pump option for larger offices.

Total cost for a typical 20m² London garden office electrical: £1,800-3,500 including sub-main, sub-board, internal circuits, lighting and certification.

Outdoor sockets and lighting

Single outdoor socket on the rear of the house — typical install £180-280. Branch from existing kitchen ring main via a spur and an IP-rated socket.

Outdoor double socket on a free-standing pillar — £350-550 install. SWA run from house, mounted on a small concrete plinth.

Garden lighting — typically low-voltage (12V or 24V) for safety and ease of install. Transformer in the house or in an IP-rated outdoor enclosure.

Mains-voltage garden lighting needs IP65 fittings, SWA cable runs, and proper earth bonding. Use only for accent or pathway lights where low-voltage is impractical.

EV charger in the garden

Driveway-mounted EV charger — typical install. SWA from the house consumer unit, charger pedestal-mounted or wall-mounted on a garden wall.

Detached garage charger — SWA sub-main to the garage, sub-board in the garage with the charger circuit.

Charging cable must reach the car. Tethered chargers (Ohme Home Pro, Hypervolt 3 Pro tethered) are convenient; untethered allows any cable.

Earthing — every EV charger needs Type A RCD or Type B + DC monitoring per Reg 722. On a PME supply, also needs TT earth electrode or DC monitoring.

Cost — £900-1,500 install for a wall-mounted charger 15m from the consumer unit, less the £350 OZEV grant where eligible.

Common EICR findings on garden installs

C2 — outdoor socket without RCD protection. Common in pre-2010 installs.

C2 — SWA gland loose or damaged at house entry. Earth bonding compromised.

C2 — cable buried at less than 200mm without conduit. Risk of mechanical damage.

C3 — Type AC RCD on a circuit serving an EV charger. Recommend Type A RCBO.

C3 — outdoor lighting with cable run not protected against UV degradation. Recommend SWA or conduit-protected run.

FI — outdoor circuit termination not visible (e.g. buried junction box). Investigate to confirm safety.

Author byline

James Whitfield, Director & Qualifying Supervisor

NICEIC Approved Qualifying Supervisor, JIB Gold Card Electrician, 10+ years industry experience. Personally reviews every certificate and article published under Electrician London.

Related services

Ready to book?

Same-day NICEIC certificates across every London postcode. Director-led, no call-centre.

Call 020 3633 5557